Virtual planning
Put together your individual van racking system.
Leakage current: 5μA ... 10mA DC/AC, 50Hz ... 1MHz
Insulation faults can cause leakage currents that can potentially endanger the operator or user of an electrical device. This state of the art leakage current meter offers a first class solution to ensure the protection and safety of electrical products.
Developed to meet the specific requirements of industry, it enables efficient measurement under a wide range of operating modes.
An external input is available to supply test objects with a wide range of voltages. Thanks to its robust design and simple operation, it is the ideal choice for demanding environments.
The leakage current measurements are only possible in conjunction with the elution two software.
Measuring bandwidth: 5 µA ... 10 mA DC / AC, 50Hz ... 1MHz
3 leakage current measuring ranges: 0.1mA / 1mA / 10mA
Measurement types: I_trms, I_ac, I_dc, I_peak, I_mad (depending on the test standard used)
Fixed measuring range according to I_lc_max or automatic measuring range adjustment
External power supply
50V ... 280V AC, 1-phase, max. 15A (rev. fused), 50 ... 400Hz
Monitoring of the supply voltage of the device under test with min./max. values
Monitoring the current consumption of the device under test with min. values
Optional with supply unit
1s ... 1d adjustable in 0.1s steps
Variable test sequence
Normal operation without error
Normal operation with N error
Normal operation with PE error
Reverse polarity operation without error
Reverse polarity operation with N error
Reverse polarity operation with PE error
DUT connection, 1-phase, vi1, vi2
Additional connections for tests according to EN60601-1, MED
External supply (DUT)
Ethernet interface (RJ45 socket)
Warning lamp set connection
Remote control connection Remove Control with display
Digital input / output connection
230 V +/- 10 %; 49 .. 61 Hz
Integration in control cabinets via 6-point rack mounting
Width: 426mm
Height: 220mm
Depth: 235mm
8.5 kg
Elution Device
N2-4D
Test standard EN60335-1, 1-phase / status 08-2020
SM-EN60335-20-1
Test standard EN60335-1, 1/3-phase / Version 02-2020
SM-EN60335-20-1
Test standard EN60598-1, 1-phase / Version 03-2022
SM-EN60598-22-1
Test standard EN60601-1, 1-phase / Version 12-2013
SM-EN60601-13-1
Test standard EN60601-1, 1/3-phase / Version 12-2013
SM-EN60601-13-3
Test standard EN60601-1, 1-phase with medical supplement
SM-EN60601-13-1M
Test standard EN60601-1, 1/3-phase with medical add-on
SM-EN60601-13-3M
Test standard EN60730-1, 1-phase / status 10-2009
SM-EN60730-09-1
Test standard EN61010-1, 1-phase / Version 03-2020
SM-EN61010-20-1
Test standard EN61010-1, 1/3-phase / Version 03-2020
SM-EN61010-20-3
Test standard EN61588-1, 1-phase / status 08-2010
SM-EN61588-10-1
Test standard EN61588-1, 1/3-phase / Version 08-2010
SM-EN61588-10-3
Test standard EN62368-1, 1-phase / Version 05-2021
SM-EN62368-21-1
Test standard EN62368-1, 1/3-phase / Version 05-2021
SM-EN62368-21-3
Test standard EN62481-1, 1-phase / Version 04-2014
SM-EN62481-14-1
Test standard EN62481-1, 1/3-phase / Version 04-2014
SM-EN62481-14-3
Further test standards on request
Remote control with 6m connection cable
SM-ACC-10
Warning light red / green
SM-ACC30